Adapter
SN Adapter Non-Shuttered SC Footprint
Non-shuttered SN adapter in the SC simplex footprint, so SN ports can drop into legacy cut-outs without new panels.
- High density
Click the photo to enlarge
Shuttered SN adapter in the SC footprint, 2-channel or 4-channel, with internal shutters on every port.
The SN shuttered adapter in an SC footprint is a panel-mount coupler that joins SN duplex connectors and closes a shutter over each empty channel. It comes as a 2-channel (4 fibre) or 4-channel (8 fibre) part sized to fit existing SC-style openings. It suits operators who want very small form factor density without re-cutting a panel.
| Type | SN adapter, shuttered |
|---|---|
| Footprint | SC |
| Channels | 2-channel (4 fibre) or 4-channel (8 fibre) |
| Shutter | Internal shutters |
| Typical insertion loss | 0.10 dB |
| Maximum insertion loss | 0.20 dB |
| Operating temperature | -40 to +75 C |
| Humidity resistance | 95 percent |
| Durability | 200 matings per GR-326-Core |
| Sleeve | Precision zirconia |
Figures are the manufacturer's published values for the product family and grade; check the data sheet for the exact part number you order. Radix confirms the build in your quote.
| Channels | 2-channel (4 fibre), 4-channel (8 fibre), or other on request |
|---|---|
| Packaging and labelling | On request |
Radix supplies this part loose, or built into patch cords, pigtails and assemblies to your drawing, quoted by form, phone or WhatsApp from Pune.
Send us:
Add this part to your list, add more parts, then send one request.
The SN shuttered adapter SC footprint is an adapter body for the SN connector, a very small form factor duplex connector, built with the outer shape of an SC-style adapter so it drops into panels and bulkheads that were cut for SC. Inside, it holds two or four SN duplex channels, which means four or eight fibres. Each channel has a shutter that closes when no connector is plugged in.
It is one of several SN adapter bodies. The wider range is described on the SN connectors hub page, and the whole this range that Radix can supply is listed on the these connectors overview. The reason this body exists is practical: many data centres and telecom rooms already own thousands of SC-sized openings. Re-cutting metalwork is slow and it changes the panel. A body that fits the existing opening lets the fibre density go up without touching the chassis.
The manufacturer gives typical insertion loss of 0.10 dB and a maximum of 0.20 dB for its SN adapters, an operating range of -40 to +75 C, resistance to 95 percent humidity, and 200 matings under GR-326-Core. The sleeves are precision zirconia. Treat these as maker figures and ask for the data sheet that matches the exact order.
An SC-sized opening is a common standard across patch panels, wall boxes and optical distribution frames. The shuttered SN body is meant for those places. You put the adapter in the opening, you plug SN duplex connectors in from either face, and you get a two-fibre or four-fibre run per channel.
The shutter has two jobs. It keeps dust out of the open sleeve when a channel is not in use, and it blocks light from an active transmitter, which is a safety point when ports are live. Both are routine reasons to choose shuttered adapters on a front panel that technicians touch often. A shutter is not a substitute for a dust cap on a loose connector, and it does not make cleaning optional.
The 2-channel and 4-channel versions sit in the same outline. Pick 4-channel where the aim is density, and 2-channel where you want fewer fibres per opening, for example on a panel that will be filled slowly. The mixed approach is common: 4-channel in the dense rows, 2-channel at the edges of a build.
If you are weighing this against the standard-footprint shuttered part, read the page for the standard SN shuttered adapter alongside this one. They share the SN connector, so the choice is about the panel, not the plug.
| Part | Shutter | Channels | Fibres | Outline | Typical use |
|---|---|---|---|---|---|
| SN shuttered adapter SC footprint (this page) | Yes | 2 or 4 | 4 or 8 | SC style | Retrofit into SC-sized openings, front panels |
| SN adapter, SC footprint | No | Per data sheet | Per data sheet | SC style | SC-sized openings where shutters are not wanted |
| SN shuttered adapter | Yes | Per data sheet | Per data sheet | SN standard | New panels built for SN |
| SN non-shuttered adapter | No | 1 or 4 | 2 or 8 | SN standard | Coherent optics, single separated channel |
Where the table says "per data sheet", Radix does not quote a figure here. The point of the table is the decision path: shutter or not, then panel outline, then channel count.
A shutter closes the path for dust when a channel is empty. It does not clean the end face of a connector you are about to insert, and it can carry its own debris on the inside of the flap. Inspect and clean every connector end face before it goes into the sleeve, as the end face cleaning and inspection guide describes.
Very small form factor connectors have little room for a finger or a tool. Allow for the width of your fingers when you plan the density of a panel. Push-pull style boots help in tight rows, and you should still leave space to pull a connector straight out, not at an angle, so the ferrule does not scrape the sleeve.
When a channel will stay empty for a long time, leave the shutter closed and do not prop it open with a probe. If you must inspect a port, use a probe made for the SN size and close the shutter after. Keep a record of which ports are live before you open any channel.
Assume a 1U panel has 12 openings cut for SC adapters, and the data sheet confirms the 4-channel SN body fits that outline. These are assumed figures for illustration, not a Radix quotation.
Now add a loss check. A link with two mated pairs uses the adapter loss twice. At the manufacturer typical figure of 0.10 dB, two adapters contribute about 0.20 dB, and at the 0.20 dB maximum, about 0.40 dB. Put the maximum figure in the loss budget for a worst case, and the typical figure for expected performance. Connector loss in the plugs themselves is added on top.
The saving is real only if the connectors, trunks and cassettes behind the panel also move to SN, so cost the whole chain, not the adapter alone.
The adapter takes SN duplex connectors on both faces. The manufacturer states that SN Uniboot is only compatible with the standard SN footprint 4-channel adapters, so do not assume it mates in an SC-footprint body. Check before ordering the SN Uniboot connector with this adapter. The other SN connector styles, such as the SN 1.6 mm standard connector, are covered on their own pages.
Also confirm these points with the data sheet:
Where an SN link ends in a transceiver cage instead of a panel, the SN gang clip for transceivers is a related part, not a substitute for this adapter.
Radix can supply this adapter loose, or fitted to a panel or cassette to your drawing. For a quotation by form, phone or WhatsApp from Pune, send:
Radix tests each cord before dispatch. Use the request a quote form or call +91 99702 02526 in office hours. For cords with SN ends, see custom fibre optic assemblies.
It is a panel adapter that joins SN duplex connectors and has a shutter over each channel. The outer body is shaped like an SC-style adapter so it fits existing SC-sized openings. It comes in 2-channel (4 fibre) and 4-channel (8 fibre) versions.
The 2-channel version carries four fibres and the 4-channel version carries eight. Each channel is one SN duplex pair. The totals per panel follow from how many openings you have.
The manufacturer gives a typical insertion loss of 0.10 dB and a maximum of 0.20 dB for its SN adapters. Use the maximum in a worst-case budget and the typical figure for expected results. Connector loss is added separately.
No. The shutter protects an empty channel from dust and blocks light from a live transmitter. It does not clean a connector end face. Inspect and clean every connector before mating.
The manufacturer states that SN Uniboot is only compatible with standard SN footprint 4-channel adapters. That suggests it does not suit an SC-footprint body, but check the data sheet before ordering.
Yes, if each adapter fits its own opening and you label the panel clearly. The connectors do not interchange, so a mixed panel needs careful port labelling. Cords must match the adapter at each end.
The 200 matings figure refers to durability under GR-326-Core for SN adapters. It is a test-based figure, not a promise of life in your site. Cleaning habits affect real life more than the count.
Send quantities by channel count, fibre type, polish, the panel model or opening drawing, and any cords you need built with it. Use the quote form, phone or WhatsApp. Radix replies with a quotation from Pune.
Send the part, quantity and drawing. An engineer replies with questions or a quote.
Fill in what you know. An engineer replies from sales@radixfibrotech.com, Monday to Friday, 09:00 to 18:00 India time. Prefer to talk? Call +91 99702 02526.
Your reference is . A confirmation is on its way to your inbox. We reply from sales@radixfibrotech.com, Monday to Friday, 09:00 to 18:00 India time.
Urgent, or have a drawing? Send the reference on WhatsApp and we will pick it up there.